3. BCU2002 Battery Connection
BCU2002 measures no cells itself: the cells and the temperature sensors of the pack are wired to BMS1802 or BMS1202 slave modules, up to 16 of them, and the BCU2002 reads them over the isolated daisy chain. The BCU2002 measures the pack current, switches the contactors and talks to the rest of the system. This page first shows the BCU2002 in a typical battery system, then how to wire the supply and the button, the communication ports, the outputs and inputs, the slave modules, the devices on the communication lines and the current sensor, and what to set in LiMon™ afterwards. The connector numbers are those of the pinout.
3.1 BCU2002 in a Battery System
In a typical system the slave modules sit on the pack and measure its cells and temperatures; the BCU2002 reads them over the daisy chain on connector 15 and measures the pack current with a Hall sensor on the negative cable. It switches a separate discharge path to the load, with a precharge branch, and a charge path to the charge socket; three of its high-side outputs drive the coils of the charge, discharge and precharge contactors through mini relays. The sense contact of the charge socket goes to isolated input 1, set to CHG Power Path Interlock, so that the pack cannot discharge while the charge cable is plugged in. The BCU2002 talks to the inverter, the charger and a DIS700 or DIS110 display over CAN, to a PC with LiMon™ over the service port and to a Modbus master over RS485; its relay can drive an alarm lamp.
Fig.3.1.1: BCU2002 in a Typical Battery System
Tip
The figure uses layout C of User Manual 3.8 Power Path: separate charge and discharge contactors with a charge interlock. One main contactor for both paths is layout A there; the precharge itself is in User Manual 3.9 Precharge.
3.2 Power Supply and User Button
BCU2002 runs from 12 to 80 V on VIN+ of connector 1 or from a 12 V supply on 12Vin of connector 2. Use one of the two, never both at the same time. It measures no cells, so the supply does not have to come from the pack: a pack of 80 V or less, a tap of the pack that stays at 80 V or below, or a separate supply all work. The board starts with a press of the user button, a push-button between VIN+ (connector 1 pin 2) and BUTTON (pin 3); connector 2 pin 4 is the same button input for a button that sits elsewhere, and an external LED goes from LED+ (connector 2 pin 5) to LED- (pin 2).
Fig.3.2.1: BCU2002 Supply and User Button
Tip
What the button does after the start, and how the board shuts itself down, is in User Manual 3.11 Button and Shutdown.
3.3 Communication Ports and Termination Switch
RS232 (the service port for LiMon™) and RS485 are on connector 5, CAN on connector 4, all isolated from the board supply. Use CAN CH1 on pins 3 and 4; CAN CH2 on pins 1 and 2 is not used by the current firmware. The service port goes to a PC through an INT201 with its transmit and receive lines crossed, RS485 connects A to A and B to B. The settings of the ports are in User Manual 4.1 Communication Ports.
Fig.3.3.1: BCU2002 Communication Port Wiring
CAN and RS485 are lines with a 120 Ω termination at each of their two ends. The termination switch SW1 has one lever for each line: lever 2 terminates RS485, lever 4 terminates CAN CH1, lever 3 CAN CH2 and lever 1 is not used. Set a lever ON only when the BCU2002 sits at an end of that line.
Fig.3.3.2: BCU2002 Termination Switch SW1
3.4 Outputs and Inputs
The four high-side switches on connector 17 (OUT 2 to OUT 5) drive mini relays and other small loads, not contactor coils: a contactor is switched by the contact of a mini relay, from its own supply. The outputs switch the 12 V of the board, or an external supply on Vext (pin 10) when it is above 12 V, for example 24 V for mini relays with a 24 V coil; the loads and the minus of the Vext supply return to GND on pins 1 to 5. The relay on connector 18 (OUT 6) is a free contact (COM, N.O., N.C.). Connector 3 carries the two isolated inputs and the isolated TTL output OUT 1 with their own ISO GND on pins 1 to 3: an input is active while it is at ISO GND, through a closed contact or a 0 V logic signal (5 V or open is inactive), and the TTL output gives a signal, not the current for a load. What each output and input does is set in LiMon™; see User Manual 3.10 Inputs and Outputs, whose Table.3.10.4 lists the pin of every LiMon™ number.
Fig.3.4.1: BCU2002 Output and Input Examples
Warning
Do not connect a contactor coil straight to a high-side output; use a mini relay. This manual gives no current rating for the outputs, so check any other load with LiBat™ first.
3.5 Slave Modules via Isolated Daisy Chain Communication Port
BCU2002 drives up to 16 BMS1802 or BMS1202 slave modules over the isolated daisy chain on RJ45 connector 15. The start of the line is terminated on the BCU2002 board. The BCU2002 has no cells of its own, so the first slave is Module ID#0. Connector 16 is an optional second RJ45 port and is not used here.
Fig.3.5.1: BCU2002 Isolated Daisy Chain to the Slave Modules
Tip
Use CAT5e or CAT6 cable, up to 50 m. The cells and the temperature sensors are wired to the slaves; how each slave is wired, how it takes its module ID and how the line end is closed is on its own page: BMS1802 Battery Connection or BMS1202 Battery Connection.
3.6 Devices on the Communication Lines
The CAN line on connector 4 carries the inverter or motor controller, a CAN charger, a DIS700 or DIS110 display and, in a system with packs in parallel, the other packs. The RS485 line on connector 5 carries a Modbus master, such as a PLC, an HMI, a SCADA system or a gateway, and any other Modbus device with its own address. The service port is a point-to-point link to a PC with LiMon™ through an INT201. A charger on CAN is set up as in User Manual 4.2 Charger Integration, packs in parallel as in User Manual 4.3 Parallel Packs.
Fig.3.6.1: BCU2002 Devices on the Communication Lines
3.7 Current Sensor Connection
A Hall current sensor with a 5 V supply connects to connector 12, Current Sensor No#1: its output to CS1-CH1 (pin 1), a second range of a dual-channel sensor to CS1-CH2 (pin 2), its supply to CS-ISO-5V (pin 3) and CS-ISO-GND (pin 4). The sensor supply is isolated from the board. Connector 11, Current Sensor No#2, is not used for the pack current. The figure shows a LEM DHAB S/133, a dual-channel sensor whose high range goes to Ch#1 and its low range to Ch#2. The sensor type, the channels and the coefficients are set in LiMon™; see User Manual 3.6 Current Measurement, which gives the values of this sensor on a BCU2002.
Fig.3.7.1: BCU2002 Current Sensor Connection, LEM DHAB S/133
3.8 Settings in LiMon™ and First Check
After the wiring, set the slave modules in LiMon™ and restart the BCU2002 so that it finds them:
- Slave Module Type Selection: BMS1802 or BMS1202. All slaves of one BCU2002 are the same type.
- Module ID#n: the cell count of every slave module, from ID#0 up, up to 16 modules; a BMS1802 takes its ID from its place in the chain, a BMS1202 from its ADDRESS switch (User Manual 3.1 Battery Topology).
- Save, restart the BCU2002 and check in Live View that every module is there with the cell count you set. The full procedure is in 2.1 Commissioning Checklist.
Table.3.8.1: Wiring Faults and What the BCU2002 Reports
| Wiring fault | Event | What to check |
|---|---|---|
| A cell tap missing or loose on a slave, an unused input of a slave not tied to its highest cell, or a cell count in LiMon™ that does not match | (26) Cell Connection Error | Connected Cells of the module, then its cell connector and the cell count in LiMon™ |
| A daisy chain cable or connector broken, or a slave module below 11 V | (29) Slave Module Communication Error | Which module is missing in Live View, then its cables and its cell voltages |
| A temperature sensor on a slave not connected or its wire broken | none; the input is ignored | That the sensor reads a value in Live View |
After a fault is repaired, restart the BCU2002. All events and their causes are in 6.1 Events and What to Do.